Test your basic knowledge |

NATE Air Conditioning Troubleshooting

Subjects : engineering, nate
Instructions:
  • Answer 50 questions in 15 minutes.
  • If you are not ready to take this test, you can study here.
  • Match each statement with the correct term.
  • Don't refresh. All questions and answers are randomly picked and ordered every time you load a test.

This is a study tool. The 3 wrong answers for each question are randomly chosen from answers to other questions. So, you might find at times the answers obvious, but you will see it re-enforces your understanding as you take the test each time.
1. What controls are used on air conditioning or refrigeration systems that incorporate an automatic pump-down system...






2. A liquid-charged TXV bulb will...






3. What are common methods that are used for leak-testing a system...






4. What type of problems can be caused by an oversized air conditioning system...






5. What problem or problems can cause low discharge and suction pressure...






6. When troubleshooting a split-system air conditioner - it is found that the compressor motor is humming but not starting. Technician A says that it could be an open internal overload protector. Technician B says that it could be a blown fuse. Which te






7. What are two problems that can cause an air conditioning system to have an excessively high superheat...






8. If a TXV sensing bulb had lost its charge - what effect would this have on the air conditioning system...






9. A system that is operating with a clear sight glass shows...






10. A customer calls and complains that her high-efficiency air conditioning system is operating - but is not cooling properly. Further investigation shows that the system is using a TXV type of metering device. A subcooling check shows that the system a






11. What three things can prevent an air conditioning system from releasing heat at the proper rate...






12. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...






13. What three things can prevent an air conditioning system from absorbing heat at the proper rate...






14. Which of the following could be the cause for a system's discharge and suction pressure being low...






15. What problem or problems can cause the discharge pressure to be low and the suction pressure to be high...






16. Which of the following is a possible cause for a compressor to overheat...






17. What is the purpose of a CPR valve...






18. The technician observes a pressure drop of 25 degrees across an air conditioning evaporator coil at start-up. This drop would indicate...






19. What causes the automatic expansion valve to close...






20. A system that is operating with a clear sight glass shows...






21. A system that is being serviced has been evacuated down to 500 microns. When the gauges are closed and the vacuum pump is turned off - the pressure starts to increase and stops at 1000 microns. Technician A says that the system has a leak and needs t






22. A commercial customer calls on a 90






23. A compressor motor starts and operates for a short period of time and cycles on the external overload protector. What are two possible problems that could cause this...






24. A liquid-charged TXV bulb will...






25. A hard-start kit consists of...






26. Which of the following can cause low superheat in a TXV system...






27. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro






28. The internal overload of an air conditioning compressor senses winding temperature and...






29. A technician arrives on the job and the customer complains that there is no cooling on his rooftop unit. Troubleshooting the system - the technician finds that the compressor is faulty. He notices that there is another faulty compressor laying next t






30. What are the symptoms of an air conditioning system that has a bad compressor discharge valve...






31. When an air conditioning system has an undercharge - what happens to the superheat and the subcooling of the system...






32. On an are-22 air conditioning system - the suction-line filter drier should be changed when the pressure drop dictates...






33. Why is it unsafe to operate an air conditioning system with a low charge...






34. What are two common symptoms of refrigerant leaks in an air conditioning system...






35. What are the symptoms of an air conditioning system that has a low charge...






36. What problem can cause an increase of discharge pressure and an increase of suction pressure...






37. A split-system air conditioner that uses a piston-type metering device is to be charged with are-22. Technician A says that the outdoor dry-bulb temperature is needed to determine the proper superheat. Technician B says that the indoor wet-bulb tempe






38. What are two common symptoms of refrigerant leaks in an air conditioning system...






39. Which of the following is a common cause of an excessively low superheat on a TXV system...






40. When troubleshooting a split-system air conditioner - it is found that the compressor motor is humming but not starting. Technician A says that it could be an open internal overload protector. Technician B says that it could be a blown fuse. Which te






41. What is the common cause of a compressor burnout...






42. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the outdoor condensing unit is operating - but the indoor blower is not in operation. Technician A says that it is possible that it is a bad fu






43. Which of the following will cause excessive discharge pressures on an air conditioning system...






44. A customer calls and complains that her high-efficiency air conditioning system is operating - but is not cooling properly. Further investigation shows that the system is using a TXV type of metering device. A subcooling check shows that the system a






45. What problem or problems can cause the discharge pressure to be low and the suction pressure to be high...






46. The best description of a relay would be...






47. A customer calls and says that her air conditioning system is not cooling properly. Upon arrival - a technician notices that the suction line and compressor have frost buildup. Technician A says that the problem is probably a low charge. Technician B






48. When testing an indoor blower control circuit and the cooling circuit on a fan center - what terminals should read 24 volts if the air conditioning system is in operation...

Warning: Invalid argument supplied for foreach() in /var/www/html/basicversity.com/show_quiz.php on line 183


49. What is the purpose of the TXV...






50. What are the symptoms of a TXV air conditioning system if it has lost its charge...