SUBJECTS
|
BROWSE
|
CAREER CENTER
|
POPULAR
|
LOGIN
Business Skills
|
Soft Skills
|
Basic Literacy
|
Certifications
About
|
Help
|
Privacy
|
Terms
|
Email
Search
Test your basic knowledge |
NATE Air Conditioning Troubleshooting
Start Test
Study First
Subjects
:
engineering
,
nate
Instructions:
Answer 50 questions in 15 minutes.
If you are not ready to take this test, you can
study here
.
Match each statement with the correct term.
Don't refresh. All questions and answers are randomly picked and ordered every time you load a test.
This is a study tool. The 3 wrong answers for each question are randomly chosen from answers to other questions. So, you might find at times the answers obvious, but you will see it re-enforces your understanding as you take the test each time.
1. What controls are used on air conditioning or refrigeration systems that incorporate an automatic pump-down system...
The superheat increases and the subcooling decreases
It would cause the low-side pressure to decrease
50-65
A thermostat cycles the liquid-line solenoid - and a low-pressure switch controls the compressor
2. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro
Run with high head and high suction pressure
Always have some liquid present in the bulb and diaphragm
Technician B
Always have some liquid present in the bulb and diaphragm
3. A party-store owner tried to adjust the water valve on his water-cooled condensing unit - then he called for assistance from an HVAC/are service technician. It was found that when servicing the unit - the outlet water temperature was too low. Technic
Bad compressor valve
A missing air filter+improper rotation of the indoor blower+blower too small
Technician B
An open internal overload protector
4. When an air conditioning system has an undercharge - what happens to the superheat and the subcooling of the system...
Dirty condenser - bent condenser fins - and air recirculating over the condenser
The superheat increases and the subcooling decreases
Technician A is correct
Can use the thermal electric expansion valve instead of a liquid-line solenoid as part of the pump-down system
5. What are the symptoms of an air conditioning system that has a low charge...
The low-side pressure will decrease and the evaporator coil will be partially frosted
3 psig
A restricted metering device
A low refrigerant charge
6. The internal overload of an air conditioning compressor senses winding temperature and...
Current in the compressor circuit
Technician B
A start relay
110-120
7. A commercial customer calls on a 90
Dirty condenser - bent condenser fins - and air recirculating over the condenser
The system could be undercharged+The compressor could have bad valves+The system could have a restricted metering device
Clean the condenser coil
The system has been overcharged+The system has air trapped in the condenser
8. Which of the following problems can cause a decrease in a system's pressures and possible icing of the evaporator coil...
Low voltage and a faulty start relay
A missing air filter+improper rotation of the indoor blower+blower too small
Rise more than normal
The superheat increases and the subcooling decreases
9. Which of the following can cause low superheat in a TXV system...
A bad thermostat
Technician B
An uninsulated TXV sensing bulb
A dirty evaporator coil - a defective evaporator fan - and an iced-up evaporator coil
10. When testing an indoor blower control circuit and the cooling circuit on a fan center - what terminals should read 24 volts if the air conditioning system is in operation...
11. A system that is being serviced has been evacuated down to 500 microns. When the gauges are closed and the vacuum pump is turned off - the pressure starts to increase and stops at 1000 microns. Technician A says that the system has a leak and needs t
It is used to control refrigerant pressure in the compressor crankcase
Technician B
Whenever necessary
It keeps a constant superheat in the evaporator
12. What problem or problems can cause low discharge and suction pressure...
A bad thermostat
A sensing bulb improperly connected to the suction line
An undercharged system+insufficient airflow over the evaporator coil
Technician B
13. What are common methods that are used for leak-testing a system...
Technician B
A missing air filter+improper rotation of the indoor blower+blower too small
A restricted metering device
A vacuum test+oil traces around fittings+soap bubble solution
14. A system that uses a thermal electric expansion valve...
A plugged filter drier
Can use the thermal electric expansion valve instead of a liquid-line solenoid as part of the pump-down system
Contains a solenoid coil and one or more sets of contacts
50-65
15. What problem can cause an increase of discharge pressure and an increase of suction pressure...
An overcharged system
Short cycling and insufficient dehumidification
Both technicians are incorrect
Clean the condenser coil
16. Which of the following can cause excessive subcooling...
A dirty condenser - recirculation of condenser air - and a defective condenser fan
The sensing bulb at a lower temperature than the valve body
An overcharged system
Technician B
17. A customer calls to complain that his central air conditioning system is not cooling properly. The technician arrives on the job. He or she notices that the indoor blower has adequate airflow and the outdoor condenser fan is operating - but the compr
A low amp draw - a decrease in high-side pressure - and a decrease in low-side pressure
An open internal overload protector
Low superheat
Technician B
18. What are common methods that are used for leak-testing a system...
50-65
The system has been overcharged+The system has air trapped in the condenser
Whenever necessary
A vacuum test+oil traces around fittings+soap bubble solution
19. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the outdoor condensing unit is operating - but the indoor blower is not in operation. Technician A says that it is possible that it is a bad fu
Both technicians are incorrect
High superheat and low discharge pressure
Low discharge pressure - high suction pressure - and low amp draw
Current in the compressor circuit
20. What component is most often the cause of a start capacitor failure...
Low discharge pressure - high suction pressure - and low amp draw
Low superheat
Technician B
A start relay
21. Insufficient airflow can be caused by...
A dirty evaporator coil+a plugged air filter+a bad indoor blower relay
The system has been overcharged+The system has air trapped in the condenser
Condenser air being recirculated over the condenser+air trapped in the condenser due to poor service procedures+an overcharged air conditioning system
An increase of air leakage from ductwork
22. A liquid-charged TXV bulb will...
Always have some liquid present in the bulb and diaphragm
An uninsulated suction line and a restricted metering device
('Y' and 'C') and ('G' and 'C')
The system was improperly serviced and it has air trapped in the condenser or the unit has been overcharged
23. A split-system air conditioner that uses a piston-type metering device is to be charged with are-22. Technician A says that the outdoor dry-bulb temperature is needed to determine the proper superheat. Technician B says that the indoor wet-bulb tempe
Both technicians are correct
Both technicians are incorrect
The external equalizer could be plugged
'G' to 'C'
24. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...
The superheat increases and the subcooling decreases
Condenser fans operating during a low ambient condition and a low suction pressure
Technician B
A bad thermostat
25. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro
Rise more than normal
It is used to control refrigerant pressure in the compressor crankcase
Technician B
Increases starting torque
26. What is a common temperature difference between the condensing temperature on an air-cooled condensing unit and the outdoor ambient temperature...
Both technicians are correct
Technician B
Dirty condenser - bent condenser fins - and air recirculating over the condenser
20 to 30
27. What are possible problems that can cause the discharge-line temperature on an air conditioning system to be cool to the touch...
('Y' and 'C') and ('G' and 'C')
Technician B
Increases starting torque
The system could be undercharged+The compressor could have bad valves+The system could have a restricted metering device
28. A compressor having tight bearings would cause the current value to...
An overcharged system
A restricted metering device
Rise more than normal
Whenever necessary
29. A liquid-charged TXV bulb will...
Can use the thermal electric expansion valve instead of a liquid-line solenoid as part of the pump-down system
An open internal overload protector
Always have some liquid present in the bulb and diaphragm
A plugged filter drier
30. A hard-start kit consists of...
A dirty evaporator coil+a plugged air filter+a bad indoor blower relay
A thermostat cycles the liquid-line solenoid - and a low-pressure switch controls the compressor
The system could be undercharged+The compressor could have bad valves+The system could have a restricted metering device
A start capacitor and a solid-state relay
31. A customer calls and complains that her high-efficiency air conditioning system is operating - but is not cooling properly. Further investigation shows that the system is using a TXV type of metering device. A subcooling check shows that the system a
Technician A is correct
The external equalizer could be plugged
Improper system evacuation during installation+short cycling of the system+excessively dirty condenser
Current in the compressor circuit
32. A system that is operating with a clear sight glass shows...
The sight glass is full of liquid+the sight glass is full of gas
A low refrigerant charge
Broken rings+broken valves+seized bearings
A start capacitor and a solid-state relay
33. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the system is using are-22 with the high-side pressure at 290 psig and the low-side pressure at 85 psig. The ambient temperature is 85
50-65
Technician A is correct
Technician A
3 psig
34. When an air conditioning system has an undercharge - what happens to the superheat and the subcooling of the system...
An overcharged system
The superheat increases and the subcooling decreases
A defective circuit breaker
The system could be undercharged+The compressor could have bad valves+The system could have a restricted metering device
35. Superheat is found in an air conditioning system in the...
A plugged filter drier
An open internal overload protector
Evaporator and compressor
An overcharged system
36. What is the purpose of a CPR valve...
It can seize the compressor because of excessive heat+It can seize the compressor because of lack of lubrication
A dirty evaporator coil+a plugged air filter+a bad indoor blower relay
It is used to control refrigerant pressure in the compressor crankcase
The external equalizer could be plugged
37. What controls are used on air conditioning or refrigeration systems that incorporate an automatic pump-down system...
An undercharge and low ambient conditions
Low discharge pressure - high suction pressure - and low amp draw
A thermostat cycles the liquid-line solenoid - and a low-pressure switch controls the compressor
A bad thermostat
38. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...
It can seize the compressor because of excessive heat+It can seize the compressor because of lack of lubrication
The oil pump pressure and the crankcase pressure
Condenser fans operating during a low ambient condition and a low suction pressure
Low discharge pressure - high suction pressure - and low amp draw
39. What problem or problems can cause the discharge pressure to be low and the suction pressure to be high...
The system was improperly serviced and it has air trapped in the condenser or the unit has been overcharged
High suction pressure and low superheat
Bad compressor valve
A bad thermostat
40. If 24 volts are present to the contactor coil on an air conditioning system and the condenser fan or compressor is inoperative - which of the following could be at fault...
Current in the compressor circuit
A low amp draw - a decrease in high-side pressure - and a decrease in low-side pressure
A blown fuse
Broken rings+broken valves+seized bearings
41. What component is most often the cause of a start capacitor failure...
The sensing bulb at a lower temperature than the valve body
Technician A
A start relay
It is used to control refrigerant pressure in the compressor crankcase
42. What are two common symptoms of refrigerant leaks in an air conditioning system...
Technician B
An increase in suction pressure and an increase in discharge pressure
Both technicians are correct
Partially frosted evaporator and high superheat
43. If a rooftop air conditioning system does not have any means of low ambient protection - what will be two symptoms of the system when operating under a low ambient condition...
High superheat and low discharge pressure
Current in the compressor circuit
Low voltage and a faulty start relay
A sensing bulb improperly connected to the suction line
44. A commercial customer calls complaining that her rooftop air conditioning system is not operating. The technician arrives on the job and sets the thermostat to cooling - then notices that the indoor fan is not operating. The technician then sets the
45. A compressor motor starts and operates for a short period of time and cycles on the external overload protector. What are two possible problems that could cause this...
An uninsulated TXV sensing bulb
Low voltage and a faulty start relay
Technician B
A thermostat cycles the liquid-line solenoid - and a low-pressure switch controls the compressor
46. A compressor having tight bearings would cause the current value to...
Clean the condenser coil
An increase of air leakage from ductwork
Rise more than normal
Whenever necessary
47. A hard-start kit consists of...
Whenever necessary
A start capacitor and a solid-state relay
It increases pressure in a high-temperature evaporator coil when it is used on a dual-evaporator system
Low voltage and a faulty start relay
48. On an are-22 air conditioning system - the suction-line filter drier should be changed when the pressure drop dictates...
Technician B
3 psig
The system was improperly serviced and it has air trapped in the condenser or the unit has been overcharged
Condenser air being recirculated over the condenser+air trapped in the condenser due to poor service procedures+an overcharged air conditioning system
49. What is the purpose of an EPR valve...
Partially frosted evaporator and high superheat
The sight glass is full of liquid+the sight glass is full of gas
An overcharged system
It increases pressure in a high-temperature evaporator coil when it is used on a dual-evaporator system
50. Technician A says ' When charging a system using the superheat method - adding refrigerant to the system will increase the superheat.' Technician B says 'When charging a system using the superheat method - adding refrigerant will decrease the superhe
A blown fuse
Technician B
An increase in low-side pressure
Bad compressor valve