Test your basic knowledge |

NATE Air Conditioning Troubleshooting

Subjects : engineering, nate
Instructions:
  • Answer 50 questions in 15 minutes.
  • If you are not ready to take this test, you can study here.
  • Match each statement with the correct term.
  • Don't refresh. All questions and answers are randomly picked and ordered every time you load a test.

This is a study tool. The 3 wrong answers for each question are randomly chosen from answers to other questions. So, you might find at times the answers obvious, but you will see it re-enforces your understanding as you take the test each time.
1. Air filters should be replaced...






2. An air conditioning unit has a suction line that is frosted up to the compressor. What faults could cause this to occur...






3. A compressor motor starts and operates for a short period of time and cycles on the external overload protector. What are two possible problems that could cause this...






4. What are common methods that are used for leak-testing a system...






5. When using a vapor-charged TXV bulb - it is necessary to have...






6. What are two common problems that can cause a sight glass in an air conditioning to have bubbles...






7. What causes the automatic expansion valve to close...






8. A restricted air filter in an air conditioning system can be identified by...






9. What are common methods that are used for leak-testing a system...






10. Technician A says that to manually pump down an air conditioning system with a two-position service valve - the liquid line must be front-seated and the high- and low-side pressure will decrease to 0 psig when the pump-down is complete. Technician B






11. What types of symptoms will be present if the sensing bulb of a TXV is not properly connected...






12. A commercial customer calls on a 90






13. When an air conditioning system has an undercharge - what happens to the superheat and the subcooling of the system...






14. A 220-volt 30-amp motor circuit keeps tripping the breaker after the motor is started. The starting amperage is 60 amps. When measuring the amperage of the circuit - This is drawn for a brief moment. After startup - the amperage drops to 22 amps and






15. What are possible problems that can cause the discharge-line temperature on an air conditioning system to be cool to the touch...






16. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...






17. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the system is using are-22 with the high-side pressure at 290 psig and the low-side pressure at 85 psig. The ambient temperature is 85






18. On an are-22 air conditioning system - the suction-line filter drier should be changed when the pressure drop dictates...






19. The temperature range of the suction line from an air conditioning system should be...






20. What are the symptoms of a TXV air conditioning system if it has lost its charge...






21. Which of the following problems can cause a decrease in a system's pressures and possible icing of the evaporator coil...






22. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...






23. A customer calls and complains that his air conditioning system is not operating properly. It is noticed that the compressor is not operating. A check on the run capacitor shows that there is 33 uf and the rating on the capacitor is 40 uf. Technician






24. What is the purpose of the TXV...






25. What problem or problems can cause the discharge pressure to be low and the suction pressure to be high...






26. What problem or problems can cause low discharge and suction pressure...






27. A split-system air conditioner that uses a piston-type metering device is to be charged with are-22. Technician A says that the outdoor dry-bulb temperature is needed to determine the proper superheat. Technician B says that the indoor wet-bulb tempe






28. A compressor motor starts and operates for a short period of time and cycles on the external overload protector. What are two possible problems that could cause this...






29. Technician A says that to manually pump down an air conditioning system with a two-position service valve - the liquid line must be front-seated and the high- and low-side pressure will decrease to 0 psig when the pump-down is complete. Technician B






30. The technician observes that the compressor is not operating. The compressor windings read 5 ohms start to run - run to common is opened - and start to common is opened. The technician concludes that...






31. Which of the following is a common cause of an excessively low superheat on a TXV system...






32. What is the purpose of a CPR valve...






33. What component is most often the cause of a start capacitor failure...






34. The technician observes a pressure drop of 25 degrees across an air conditioning evaporator coil at start-up. This drop would indicate...






35. What is a possible cause of a sweat or frost pattern downstream from a sight glass and filter dryer...






36. What types of symptoms will be present if the sensing bulb of a TXV is not properly connected...






37. Insufficient airflow can be caused by...






38. Which of the following is a common cause of an excessively low superheat on a TXV system...






39. Superheat is found in an air conditioning system in the...






40. An air conditioning system that uses a fan center has an inoperable indoor blower. When the thermostat is set for cooling and dialed below room temperature - a test with the voltmeter shows that there is 24 volts across terminals 'are' and 'G' at the






41. What three things can prevent an air conditioning system from absorbing heat at the proper rate...






42. What are two common problems that can cause a sight glass in an air conditioning to have bubbles...






43. When a high-efficiency split air conditioning system has a plugged metering device - what symptoms might occur...






44. The internal overload of an air conditioning compressor senses winding temperature and...






45. What are the operating pressures of an oil pressure safety switch...






46. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro






47. A technician arrives on the job and the customer complains that there is no cooling on his rooftop unit. Troubleshooting the system - the technician finds that the compressor is faulty. He notices that there is another faulty compressor laying next t






48. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the outdoor condensing unit is operating - but the indoor blower is not in operation. Technician A says that it is possible that it is a bad fu






49. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro






50. A split-system air conditioner that uses a piston-type metering device is to be charged with are-22. Technician A says that the outdoor dry-bulb temperature is needed to determine the proper superheat. Technician B says that the indoor wet-bulb tempe