Test your basic knowledge |

NATE Air Conditioning Troubleshooting

Subjects : engineering, nate
Instructions:
  • Answer 50 questions in 15 minutes.
  • If you are not ready to take this test, you can study here.
  • Match each statement with the correct term.
  • Don't refresh. All questions and answers are randomly picked and ordered every time you load a test.

This is a study tool. The 3 wrong answers for each question are randomly chosen from answers to other questions. So, you might find at times the answers obvious, but you will see it re-enforces your understanding as you take the test each time.
1. When testing an indoor blower control circuit and the cooling circuit on a fan center - what terminals should read 24 volts if the air conditioning system is in operation...


2. Insufficient airflow can be caused by...






3. What are possible problems that can cause the discharge-line temperature on an air conditioning system to be cool to the touch...






4. What type of problems can be caused by an oversized air conditioning system...






5. The internal overload of an air conditioning compressor senses winding temperature and...






6. When an air conditioning system has an undercharge - what happens to the superheat and the subcooling of the system...






7. Technician A says that to manually pump down an air conditioning system with a two-position service valve - the liquid line must be front-seated and the high- and low-side pressure will decrease to 0 psig when the pump-down is complete. Technician B






8. What are two common symptoms of refrigerant leaks in an air conditioning system...






9. Which of the following can cause low superheat in a TXV system...






10. A technician arrives on the job and the customer complains that there is no cooling on his rooftop unit. Troubleshooting the system - the technician finds that the compressor is faulty. He notices that there is another faulty compressor laying next t






11. The technician observes that the compressor is not operating. The compressor windings read 5 ohms start to run - run to common is opened - and start to common is opened. The technician concludes that...






12. Insufficient airflow can be caused by...






13. What problem can cause an increase of discharge pressure and an increase of suction pressure...






14. What is the purpose of the TXV...






15. What is the purpose of an EPR valve...






16. When troubleshooting a split-system air conditioner - it is found that the compressor motor is humming but not starting. Technician A says that it could be an open internal overload protector. Technician B says that it could be a blown fuse. Which te






17. If 24 volts are present to the contactor coil on an air conditioning system and the condenser fan or compressor is inoperative - which of the following could be at fault...






18. What controls are used on air conditioning or refrigeration systems that incorporate an automatic pump-down system...






19. An air conditioning system that uses a fan center has an inoperable indoor blower. When the thermostat is set for cooling and dialed below room temperature - a test with the voltmeter shows that there is 24 volts across terminals 'are' and 'G' at the






20. What is the common cause of a compressor burnout...






21. After a compressor motor has been severely burnt - What accessory must be added as an aid to rid the air conditioning system of acid...






22. A compressor having tight bearings would cause the current value to...






23. Air filters should be replaced...






24. What are two problems that can cause an air conditioning system to have an excessively high superheat...






25. The internal overload of an air conditioning compressor senses winding temperature and...






26. What is a common temperature difference between the condensing temperature on an air-cooled condensing unit and the outdoor ambient temperature...






27. A customer calls and says that her air conditioning system is not cooling properly. Upon arrival - a technician notices that the suction line and compressor have frost buildup. Technician A says that the problem is probably a low charge. Technician B






28. A customer calls and says that her air conditioning system is not cooling properly. Upon arrival - a technician notices that the suction line and compressor have frost buildup. Technician A says that the problem is probably a low charge. Technician B






29. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the system is using are-22 with the high-side pressure at 290 psig and the low-side pressure at 85 psig. The ambient temperature is 85






30. What are the symptoms of an air conditioning system that has a bad compressor discharge valve...






31. A system that is operating with a clear sight glass shows...






32. Which of the following could be the cause for a system's discharge and suction pressure being low...






33. A customer calls with an insufficient cooling complaint. Upon arrival to the service call it is found that the system is using are-22 with the high-side pressure at 290 psig and the low-side pressure at 85 psig. The ambient temperature is 85






34. What three things can prevent an air conditioning system from releasing heat at the proper rate...






35. If a rooftop air conditioning system does not have any means of low ambient protection - what will be two symptoms of the system when operating under a low ambient condition...






36. A liquid-charged TXV bulb will...






37. A system that uses a thermal electric expansion valve...






38. What are the operating pressures of an oil pressure safety switch...






39. What are common methods that are used for leak-testing a system...






40. If a TXV sensing bulb had lost its charge - what effect would this have on the air conditioning system...






41. What are three methods for controlling a system's high-side pressure during low ambient conditions...






42. What are the symptoms of an air conditioning system that has a bad compressor discharge valve...






43. Which of the following can cause low superheat in a TXV system...






44. What are two problems that can cause an air conditioning system to have an excessively high superheat...






45. A 220-volt 30-amp motor circuit keeps tripping the breaker after the motor is started. The starting amperage is 60 amps. When measuring the amperage of the circuit - This is drawn for a brief moment. After startup - the amperage drops to 22 amps and






46. Technician A says that if you connect 208 volts to the primary side of a 240-volt/ 24-volt transformer - the transformer will burn out. Technician B says that if you connect 208 volts to the primary side of a 240-volt/24-volt transformer - the contro






47. A commercial customer calls complaining that her rooftop air conditioning system is not operating. The technician arrives on the job and sets the thermostat to cooling - then notices that the indoor fan is not operating. The technician then sets the


48. If 24 volts are present to the contactor coil on an air conditioning system and the condenser fan or compressor is inoperative - which of the following could be at fault...






49. On an are-22 air conditioning system - the suction-line filter drier should be changed when the pressure drop dictates...






50. Air filters should be replaced...