Test your basic knowledge |

NATE Air Conditioning Troubleshooting

Subjects : engineering, nate
Instructions:
  • Answer 50 questions in 15 minutes.
  • If you are not ready to take this test, you can study here.
  • Match each statement with the correct term.
  • Don't refresh. All questions and answers are randomly picked and ordered every time you load a test.

This is a study tool. The 3 wrong answers for each question are randomly chosen from answers to other questions. So, you might find at times the answers obvious, but you will see it re-enforces your understanding as you take the test each time.
1. On an are-22 air conditioning system - the suction-line filter drier should be changed when the pressure drop dictates...






2. Name two symptoms that are common to an over-charged air conditioning system and a system that has a dirty condenser.






3. Technician A says ' When charging a system using the superheat method - adding refrigerant to the system will increase the superheat.' Technician B says 'When charging a system using the superheat method - adding refrigerant will decrease the superhe






4. If 24 volts are present to the contactor coil on an air conditioning system and the condenser fan or compressor is inoperative - which of the following could be at fault...






5. A customer calls to complain that his central air conditioning system is not cooling properly. The technician arrives on the job. He or she notices that the indoor blower has adequate airflow and the outdoor condenser fan is operating - but the compr






6. Which of the following can cause low superheat in a TXV system...






7. Which of the following is a possible cause for a compressor to overheat...






8. Why is it unsafe to operate an air conditioning system with a low charge...






9. A liquid-charged TXV bulb will...






10. What are the symptoms of an air conditioning system that has a bad compressor discharge valve...






11. What component is most often the cause of a start capacitor failure...






12. Superheat is found in an air conditioning system in the...






13. Insufficient airflow can be caused by...






14. What is the purpose of a CPR valve...






15. What are two common symptoms of an overcharged air conditioning system that uses a capillary-tube-type metering device...






16. What is the purpose of an EPR valve...






17. What problem can cause an increase of discharge pressure and an increase of suction pressure...






18. The technician observes a pressure drop of 25 degrees across an air conditioning evaporator coil at start-up. This drop would indicate...






19. When testing an indoor blower control circuit and the cooling circuit on a fan center - what terminals should read 24 volts if the air conditioning system is in operation...

Warning: Invalid argument supplied for foreach() in /var/www/html/basicversity.com/show_quiz.php on line 183


20. The technician observes that the compressor is not operating. The compressor windings read 5 ohms start to run - run to common is opened - and start to common is opened. The technician concludes that...






21. What are three methods for controlling a system's high-side pressure during low ambient conditions...






22. What problem or problems can cause low discharge and suction pressure...






23. When testing an indoor blower control circuit and the cooling circuit on a fan center - what terminals should read 24 volts if the air conditioning system is in operation...

Warning: Invalid argument supplied for foreach() in /var/www/html/basicversity.com/show_quiz.php on line 183


24. What are the symptoms of an air conditioning system that has a bad compressor discharge valve...






25. What are two common symptoms of an overcharged air conditioning system that uses a capillary-tube-type metering device...






26. When troubleshooting a split-system air conditioner - it is found that the compressor motor is humming but not starting. Technician A says that it could be an open internal overload protector. Technician B says that it could be a blown fuse. Which te






27. A technician receives an air conditioning service call stating that the system is operating but isn't cooling properly. When the technician arrives - she notices that the compressor has recently been changed and it is an are-22 system. She checks the






28. What causes the automatic expansion valve to close...






29. What causes the automatic expansion valve to close...






30. What are possible problems that can cause the discharge-line temperature on an air conditioning system to be cool to the touch...






31. A hard-start kit for an air conditioning system...






32. Technician A says that to manually pump down an air conditioning system with a two-position service valve - the liquid line must be front-seated and the high- and low-side pressure will decrease to 0 psig when the pump-down is complete. Technician B






33. A hard-start kit consists of...






34. If a rooftop air conditioning system does not have any means of low ambient protection - what will be two symptoms of the system when operating under a low ambient condition...






35. A technician arrives on the job and the customer complains that there is no cooling on his rooftop unit. Troubleshooting the system - the technician finds that the compressor is faulty. He notices that there is another faulty compressor laying next t






36. What is a common discharge temperature of an air-cooled air conditioning system that is used on a 90






37. A customer calls to complain that his central air conditioning system is not cooling properly. The technician arrives on the job. He or she notices that the indoor blower has adequate airflow and the outdoor condenser fan is operating - but the compr






38. A compressor having tight bearings would cause the current value to...






39. A customer calls with an insufficient cooling complaint on a 90






40. A customer who owns a split air conditioning system complains that his system has been running but his house doesn't seem to be cooling properly. When the service technician arrives on the job - he or she finds that the indoor blower is operating and






41. A hard-start kit for an air conditioning system...






42. What are possible problems that can cause the discharge-line temperature on an air conditioning system to be cool to the touch...






43. What are two common symptoms of a rooftop air conditioning system that operates with a reverse-acting high-pressure control stuck in the closed position...






44. What controls are used on air conditioning or refrigeration systems that incorporate an automatic pump-down system...






45. A commercial customer calls complaining that her rooftop air conditioning system is not operating. The technician arrives on the job and sets the thermostat to cooling - then notices that the indoor fan is not operating. The technician then sets the

Warning: Invalid argument supplied for foreach() in /var/www/html/basicversity.com/show_quiz.php on line 183


46. The temperature range of the suction line from an air conditioning system should be...






47. The internal overload of an air conditioning compressor senses winding temperature and...






48. A split-system air conditioner that uses a piston-type metering device is to be charged with are-22. Technician A says that the outdoor dry-bulb temperature is needed to determine the proper superheat. Technician B says that the indoor wet-bulb tempe






49. A system that uses a thermal electric expansion valve...






50. A customer calls and says that her air conditioning system is not cooling properly. Upon arrival - a technician notices that the suction line and compressor have frost buildup. Technician A says that the problem is probably a low charge. Technician B